SIPART DR19
C73000-M7474-C34-4
40
8.6
6DR2801-8D (2DO Rel.)
Required settings in the basic unit:
2DO relay module in slot 3: S22=3
Allocation of the signals to DO3 and DO4: S59 to S75
Logic of the signals: S76 to S82
The relay contacts are only approved for switching
voltages up to 35 V AC/DC!
5
497
4
496
6
495
DO4
1
μ
1
μ
22
Ω
3
397
2
396
1
395
DO3
1
μ
1
μ
22
Ω
Terminal AC contact rating
U
≤
35 V
I
≤
5 A
max. power
≤
150 VA
Terminal DC contact rating
U
≤
35 V
I
≤
5 A
max. power
≤
80 W at 35 V
≤
100 W at 24 V
Terminal blocks
Designation according
to DIN 45140
2x
68
V
A
C.....
........
2x
68
V
A
C.....
........
Configuration
switches
Important
!