4.17.5
SME120 connections
Connections
Requirements: The control cabinet is in a no-voltage condition, all of the connectors and cables
are labeled.
3URWHFWLYHFRQGXFWRU
FRQQHFWLRQ
01PPPt
;
;
;
;
X100 Encoder system interfaces, tightening torque: 3.5 Nm
X200 Temperature sensor input, tightening torque: 2 Nm
X300 Hall sensor input, tightening torque: 3.5 Nm
X500 DRIVE-CLiQ
Figure 4-60
SME120 connections
4.17.6
This is how you remove an SME120 and install it again
Removing
Procedure:
1. Release the encoder connecting cable X100 of the SME120.
2. Withdraw the DRIVE-CLiQ cable from X500 of the SME120.
3. Release the Hall sensor input X300 of the SME120.
4. Release the temperature sensor input X200 of the SME120.
5. Release the protective conductor connection of the SME120.
6. Remove the defective SME120 module.
Installing
Procedure:
1. Now install the new SME120 module.
2. Screw on the protective conductor connection.
3. Reconnect the temperature sensor at X200.
Service cases - hardware
4.17 Sensor Modules External
Software and hardware
Service Manual, 08/2018, 6FC5397-5DP40-6BA1
217