5 External interface
SINAUT MD741-1
C79000-G8976-C236-05
61
Current monthly byte count
This counter shows the data volume in bytes that was transferred via the
SINAUT MD741-1 since the beginning of the month.
On the first of the month, the counter is automatically reset. If you click the "Reset"
button, the counter is set to 0 manually.
Maximum bytes per month
Enter the limit value for the monthly data volume in bytes in the input box.
In the factory settings, the value is set to 1,000,000 bytes.
Send SMS when 80% of the max. data volume is reached
If you want the SINAUT MD741-1 to send a warning SMS message as soon as 80
% of the data volume has been reached, make the following settings:
1. Enable the SMS function by selecting the "Yes" option from the drop-down list.
2. Enter the call number of a subscriber that can receive the SMS messages.
3. If necessary change the message text from the factory settings.
4. Then click the "Save" button.
Send SMS when 100% of the max. data volume is reached
If you want the SINAUT MD741-1 to send an alarm SMS message as soon as 100
% of the data volume has been reached, make the following settings:
1. Enable the SMS function by selecting the "Yes" option from the drop-down list.
2. Enter the call number of a subscriber that can receive the SMS messages.
3. If necessary change the message text from the factory settings.
4. Then click the "Save" button.