3 Configuration
SINAUT MD741-1
32
C79000-G8976-C236-05
Assigned IP address
Shows the IP address at which the SINAUT MD741-1 can be reached in EGPRS or
GPRS. This IP address is assigned to the SINAUT MD741-1 by EGPRS or GPRS.
Connection
Shows if a wireless connection exists, and which one:
●
EDGE connection (IP connection via EGPRS)
●
GPRS connection (IP connection via GPRS)
●
CSD connection (service connection via CSD)
Note
Using connection monitoring
It is possible that you will see both an IP data connection and an assigned IP
address although the connection quality is not adequate to transfer data. For this
reason, we recommend that you use the connection monitoring. For more detailed
information, refer to the section Checking the connection - Connection monitoring
(see Chapter 5.4).
Signal strength CSQ (dbm)
The bar display and the number above it indicate the strength of the GSM signal as
a CSQ value.
CSQ = 0
No connection to the GSM network
CSQ < 6
Bad signal strength
CSQ 6 … 10
Medium signal strength
CSQ 11 … 18
Good signal strength
CSQ > 18
Very good signal strength
The dBm value is shown in brackets after the CSQ value.
If the "Installation mode" function is enabled, the display is not active..
APN in use
Shows the APN (= Access Point Name) of the wireless link that is being used.