Pump switchover
SINAMICS V20 multi-pump control
Operating Manual, 05/2018, A5E43416874-002
23
Parameter Function
Setting
P4024
Multi-pump control max time for continu-
ous operation [h]
The motor switchover will be triggered if the continuous operat-
ing hours of a motor exceed the threshold. This parameter is
used to configure the threshold value.
Default setting: 24 (minimum value: 0.1)
r4026
Multi-pump control absolute operating
hours: motor 1 [h]
Absolute operating hours timer for motor 1. It will be cleared
after re-power on.
r4027
Multi-pump control absolute operating
hours: motor 2 [h]
Absolute operating hours timer for motor 2. It will be cleared
after re-power on.
r4028
Multi-pump control absolute operating
hours: motor 3 [h]
Absolute operating hours timer for motor 3. It will be cleared
after re-power on.
r4029
Multi-pump control absolute operating
hours: motor 4 [h]
Absolute operating hours timer for motor 4. It will be cleared
after re-power on.
r4031
Multi-pump control continuous operating
hours: motor 1 [h]
Continuous operating hours timer for motor 1. It will be cleared
when the motor is switched out.
r4032
Multi-pump control continuous operating
hours: motor 2 [h]
Continuous operating hours timer for motor 2. It will be cleared
when the motor is switched out.
r4033
Multi-pump control continuous operating
hours: motor 3 [h]
Continuous operating hours timer for motor 3. It will be cleared
when the motor is switched out.
r4034
Multi-pump control continuous operating
hours: motor 4 [h]
Continuous operating hours timer for motor 4. It will be cleared
when the motor is switched out.
r4062
Inverter-controlled motor number
This parameter displays which motor is controlled by the invert-
er.
Содержание SINAMICS V20 Inverter
Страница 4: ...Table of contents SINAMICS V20 multi pump control 4 Operating Manual 05 2018 A5E43416874 002 ...
Страница 8: ...Overview SINAMICS V20 multi pump control 8 Operating Manual 05 2018 A5E43416874 002 ...
Страница 11: ...Pump switch in switch out SINAMICS V20 multi pump control Operating Manual 05 2018 A5E43416874 002 11 ...
Страница 18: ...Pump switch in switch out SINAMICS V20 multi pump control 18 Operating Manual 05 2018 A5E43416874 002 ...
Страница 24: ...Pump switchover SINAMICS V20 multi pump control 24 Operating Manual 05 2018 A5E43416874 002 ...
Страница 28: ...Faults and alarms SINAMICS V20 multi pump control 28 Operating Manual 05 2018 A5E43416874 002 ...