3.6.12
dv/dt filter (option L10)
Pulses at the drive output stress the motor insulation The dv/dt filter is used to limit the voltage
gradient to max. 1 kV/µs. At the same time, the dv/dt filter is used to limit the capacitive
recharging currents of the motor cables, and therefore protects the motor insulation system.
The dv/dt filter is integrated in the power unit.
①
Drive
②
Motor
R1,R2,R3
2.5 Ω
dv/dt filter resistance
L1, L2,L3
20 μH
dv/dt filter reactor
C1,C2,C3
1 μF
dv/dt filter capacitor
M
Center of the drive
N
Center point of the dv/dt filter
Figure 3-10
Circuit diagram option L10
Restrictions when using the output filter
● The pulse frequency of the drive must not exceed 200 Hz.
● The drive may be operated only with following maximum currents:
– 4 kA drive: 1680 A (without filter 1750 A)
– 5 kA drive: 1780 A (without filter 1850 A)
● The power loss increases by approx. 30 kW.
● The following cable length up to 200 m:
● The re-cooling unit requires 10 liter more flow
Description
3.6 Description of options
SINAMICS SM150 6SL3845-2NN41-8AD0
52
Operating Instructions Rev.201908010908 EXAMPLE
Содержание Sinamics SM150 6SL3845-2NN41-8AD0
Страница 2: ...01 08 2019 09 08 V32 00 ...
Страница 98: ...Start up SINAMICS SM150 6SL3845 2NN41 8AD0 98 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 172: ...Spare parts SINAMICS SM150 6SL3845 2NN41 8AD0 172 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 176: ...Service Support SINAMICS SM150 6SL3845 2NN41 8AD0 176 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 187: ......
Страница 190: ......
Страница 192: ......