Attaching the grounding spider
Secure the clamps for the grounding spider to the ball heads
①
and
②
.
ཱ
①
;
②
Ball heads
Figure 9-1
Attaching the grounding spider
9.2.2
Grounding using a make-proof grounding switch
The drive is equipped with a make-proof grounding switch (in compliance with the requirements
of IEC61800-5-1, Section 4.2.13).
You can close the make-proof grounding switch when the doors are closed and only at a
voltage below 60 V. If the auxiliary voltage fails completely, the make-proof grounding switch
cannot be closed. It is not permissible that you open the doors before the make-proof grounding
switch is closed.
WARNING
Danger to life as a result of a DC link short-circuit
A DC link short-circuit can occur if you ground the drive under voltage. This can result in death,
serious injury or material damage.
● Remove the socket wrench before switching on the power. This activates the interlocking.
Maintenance
9.2 Grounding the system
SINAMICS SM150 6SL3815-7NP41-0AA1
152
Operating Instructions Rev.201910281301 EXAMPLE
Содержание SINAMICS SM150 6SL3815-7NP41-0AA1
Страница 2: ...28 10 2019 13 01 V32 00 ...
Страница 116: ...Start up SINAMICS SM150 6SL3815 7NP41 0AA1 116 Operating Instructions Rev 201910281301 EXAMPLE ...
Страница 176: ...Maintenance 9 5 Repair SINAMICS SM150 6SL3815 7NP41 0AA1 176 Operating Instructions Rev 201910281301 EXAMPLE ...
Страница 178: ...Spare parts SINAMICS SM150 6SL3815 7NP41 0AA1 178 Operating Instructions Rev 201910281301 EXAMPLE ...
Страница 182: ...Service Support SINAMICS SM150 6SL3815 7NP41 0AA1 182 Operating Instructions Rev 201910281301 EXAMPLE ...
Страница 193: ......
Страница 196: ......
Страница 198: ......