SINAMICS SITOR Interface
①
Actual value output (X70)
⑫
Feedback information of the blocking volt‐
age measurement (X6)
②
A1 load
⑬
LED display (from left to right)
③
Digital potentiometer calibration JP1/2
● Pulse power supply OK
④
Actual value output (X71)
● -24 V
⑤
A2 load
● +15 V
⑥
● Firing pulse inhibit
⑦
Valve feedback signals
⑭
+24 V DC power supply,
⑧
Firing control from the PSA
Pulse power supply monitoring output
⑨
Signaling firing outputs H13 - H24
⑮
Actual value inputs (X2)
⑩
Diagnostics connector
⑯
Signaling firing outputs H1 - H12
⑪
Firing outputs (X1)
Figure 3-5
Overview of interfaces and display elements
3.2.6
TM31 Terminal Module (option C01)
The option comprises the TM31 Terminal Module. The inputs and outputs are wired as follows:
● The eight digital inputs are wired to X520 and X530.
● The analog outputs are wired to X522.
● The two relay outputs are wired to X542 on the terminal strip.
● The four bidirectional digital inputs and outputs are wired to coupling relays. The coupling
relays are also available at the terminal strip with their floating changeover contacts.
3.2.7
Three SMC30 Sensor Modules (option C02)
In addition to the three SMC30 Sensor Modules, a DMC20 DRIVE-CLiQ hub and an interface
converter are included.
The SMC30 Sensor Module cannot loop through DRIVE-CLiQ wiring. This is the reason that
the DRIVE-CLiQ hub is required. The DRIVE-CLiQ hub collects the signals from the three
Description
3.2 Options
SINAMICS SL150 6SL39616RC100AA02
34
Operating Instructions Rev.201910281458 EXAMPLE
Содержание SINAMICS SL150 6SL39616RC100AA02
Страница 2: ...28 10 2019 14 58 V18 00 ...
Страница 10: ...Table of contents SINAMICS SL150 6SL39616RC100AA02 10 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 38: ...Description 3 2 Options SINAMICS SL150 6SL39616RC100AA02 38 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 72: ...Commissioning SINAMICS SL150 6SL39616RC100AA02 72 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 86: ...Spare parts SINAMICS SL150 6SL39616RC100AA02 86 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 95: ......
Страница 98: ......
Страница 100: ......