Hard S1 materials include steel, for example.
Table 5-2
Tightening torques for screw terminals for copper cables without cable lug
1)
Screw type
Set screws and
headless screws
Head screws with
slit
Head screws with
hexagon profile
nm
in - lb
nm
in - lb
nm
in - lb
M2
-
-
-
M2.5
0.25
2.2
0.5
4.4
0.5
4.4
M3
0.3
2.7
0.6
5.3
0.6
5.3
M3.5
0.5
4.4
1.0
8.9
1.0
8.9
M4
0.8
7.1
1.3
11.5
1.3
11.5
M5
1.0
8.6
2.5
22.1
2.5
22.1
M6
1.3
11.5
3.0
26.6
3.5
31.0
M8
1.8
15.9
3.9
34.5
7.2
63.7
M10
-
-
4.8
42.5
13
115
M12
-
-
-
-
18
159.3
M16
-
-
-
-
30
265.5
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VDE 609-1
5.4
Connect to the foundation
Four holes for M12 screws are provided on each cabinet panel to secure the cabinet to the
foundation. Information on mounting holes and their fixing dimensions are specified in the
dimension drawing.
Install the transport units in accordance with the specifications provided in the accompanying
dimension drawings. When doing this, maintain the specified distance between the top of the
cabinet and the ceiling.
Mounting
5.4 Connect to the foundation
SINAMICS SL150 6SL39616RC100AA02
Operating Instructions Rev.201910281458 EXAMPLE
57
Содержание SINAMICS SL150 6SL39616RC100AA02
Страница 2: ...28 10 2019 14 58 V18 00 ...
Страница 10: ...Table of contents SINAMICS SL150 6SL39616RC100AA02 10 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 38: ...Description 3 2 Options SINAMICS SL150 6SL39616RC100AA02 38 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 72: ...Commissioning SINAMICS SL150 6SL39616RC100AA02 72 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 86: ...Spare parts SINAMICS SL150 6SL39616RC100AA02 86 Operating Instructions Rev 201910281458 EXAMPLE ...
Страница 95: ......
Страница 98: ......
Страница 100: ......