Output terminals
8.2 Analog outputs
Enclosed Drives
492
Operating Instructions, 12/2018, A5E36652151A
8.2
Analog outputs
Description
The Customer Terminal Block features two analog outputs for outputting setpoints via
current or voltage signals.
Delivery condition:
●
AO0: Actual speed value 0 to 20 mA
●
AO1: Actual motor value 0 to 20 mA
Signal flow diagram
Figure 8-1
Signal flow diagram: analog output 0
Function diagram
FP 1840,
FP 9572
TM31 - Analog outputs (AO 0 to AO 1)
Parameters
•
p4071
TM31 analog outputs signal source
•
p4073
TM31 analog outputs smoothing time constant
•
r4074
Analog outputs current output voltage/current
•
p4076
TM31 analog outputs type
•
p4077
TM31 analog outputs characteristic value x1
•
p4078
TM31 analog outputs characteristic value y1
•
p4079
TM31 analog outputs characteristic value x2
•
p4080
TM31 analog outputs characteristic value y2
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......