Fundamental safety instructions
2.1 General safety instructions
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
13
NOTICE
Material damage due to loose power connections
Insufficient tightening torques or vibrations can result in loose electrical connections. This
can result in damage due to fire, device defects or malfunctions.
•
Tighten all power connections with the specified tightening torques, e.g. line supply
connection, motor connection, DC link connections.
•
Check all power connections at regular intervals. This applies in particular after
transport.
WARNING
Danger to life due to fire spreading if housing is inadequate
Fire and smoke development can cause severe personal injury or material damage.
•
Install devices without a protective housing in a metal control cabinet (or protect the
device by another equivalent measure) in such a way that contact with fire is prevented.
•
Ensure that smoke can only escape via controlled and monitored paths.
WARNING
Danger to life from electromagnetic fields
Electromagnetic fields (EMF) are generated by the operation of electrical power equipment,
such as transformers, converters, or motors.
People with pacemakers or implants are at particular risk in the immediate vicinity of this
equipment.
•
If you have a heart pacemaker or implant, maintain a minimum distance of 2 m from
electrical power equipment.
WARNING
Danger to life through unexpected movement of machines when using mobile wireless
devices or mobile phones
Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than
approx. 2 m to the components may cause the devices to malfunction, influence the
functional safety of machines therefore putting people at risk or causing material damage.
•
Switch the wireless devices or mobile phones off in the immediate vicinity of the
components.
Содержание SINAMICS PM240-2
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Страница 104: ...Spare parts Power Module PM240 2 104 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Страница 140: ...Appendix A 4 Abbreviations Power Module PM240 2 140 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Страница 143: ......
Страница 144: ......