Setting parameters with the BOP20
4.5 Important functions via BOP20
Basic Operator Panel 20 (BOP20)
Operating Instructions, 11/2017, A5E00809375A
29
Restore the factory settings
The factory setting of the complete device can be restored in the CU drive object.
●
p0009 = 30
●
p0976 = 1
Copy from RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory (memory card) in the
drive object CU:
●
Press the "P" key for 3 seconds or
●
p0977 = 1
Note
Parameter rejection with active identification
This parameter is not accepted if an identification routine (e.g. motor identification routine)
has been selected on a drive.
Identification via LED
The main component of a drive object (e.g. power section) can be identified using the index
of p0124. The ready LED on the module starts to flash. The index corresponds to the index
in p0107; the drive object type can be identified using this parameter.
The drive objects can be identified using the following parameters:
●
p0124 Power unit detection via LED
●
p0144 Voltage Sensing Module detection via LED
●
p0144 Sensor Module detection via LED
●
p0154 DRIVE-CLiQ hub identification using LED
●
p0154 Terminal Module detection via LED
Acknowledge error
All errors whose cause has been rectified can be acknowledged by pressing the Fn key.
Содержание Sinamics G130 Basic Operator Panel 20
Страница 1: ......
Страница 2: ......
Страница 6: ...Table of contents Basic Operator Panel 20 BOP20 4 Operating Instructions 11 2017 A5E00809375A ...
Страница 16: ...General Basic Operator Panel 20 BOP20 14 Operating Instructions 11 2017 A5E00809375A ...
Страница 20: ...Installation 3 1 Removal Basic Operator Panel 20 BOP20 18 Operating Instructions 11 2017 A5E00809375A ...
Страница 34: ......