Appendix
7.3 EMC overall performance
PM230 Power Module IP55
Hardware Installation Manual, 11/2014, A5E35319202B AA
87
EMC Immunity
The SINAMICS PM230 has been tested in accordance with the immunity requirements of
category C3 (industrial) environment:
Table 7- 4
EMC Immunity
EMC Phenomenon
Standard
Level
Performance
Criterion
Electrostatic Discharge (ESD)
EN 61000-4-2 4 kV Contact discharge
A
8 kV Air discharge
Radio-frequency Electromagnet-
ic Field
EN 61000-4-3 80 MHz … 1000 MHz
10 V/m
A
Amplitude modulated
80% AM at 1 kHz
Fast Transient Bursts
EN 61000-4-4 2 kV @ 5 kHz
A
Surge Voltage
EN 61000-4-5 1 kV differential (L-L)
A
1.2/50
μs
2 kV common (L-E)
Conducted
EN 61000-4-6 0.15 MHz … 80 MHz
10 V/rms
A
Radio-frequency Common Mode
80% AM at 1 kHz
Mains Interruptions & Voltage
Dips
EN 61000-4-11 95% dip for 3 ms
A
30% dip for 10 ms
C
60% dip for 100 ms
C
95% dip for 5000 ms
C
Voltage Distortion
EN 61000-2-4
Class 3
10% THD
A
Voltage Unbalance
EN 61000-2-4
Class 3
3% Negative Phase Sequence A
Frequency Variation
EN 61000-2-4
Class 3
Nominal 50 Hz or 60 Hz
(± 45%)
A
Commutation Notches
EN 60146-1-1
Class B
Depth = 40%
A
Area = 250% x degrees
Note
The immunity requirements apply equally to both filtered and unfiltered units.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 18: ...Safety notes PM230 Power Module IP55 18 Hardware Installation Manual 11 2014 A5E35319202B AA ...
Страница 36: ......
Страница 72: ......
Страница 90: ...Appendix 7 5 Abbreviations PM230 Power Module IP55 90 Hardware Installation Manual 11 2014 A5E35319202B AA ...
Страница 93: ......
Страница 94: ......