Connecting
4.8 Gland plate installation
PM230 Power Module IP55
52
Hardware Installation Manual, 11/2014, A5E35319202B AA
Figure 4-4
Example of a Blueglobe EMC cable gland
Gland plate hole dimensions
In the table below the dimensions of the gland plate holes for all frame sizes of the PM230
are given. The cable glands are not supplied with the product but grommets are supplied
with the product.
The size of the actual cable glands should be dimensioned to fit snugly into the appropriate
cable gland hole to ensure the IP55 rating of the Inverter.
Table 4- 4
Gland plate dimensions information
Frame
size
Power range (LO) Power cable gland
diameter
Control cable gland
diameter
Cable gland manufacturers
A
0.37 ... 3.0 kW
(0.5 ... 4.0 hp)
20.5 mm
(0.80 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch
B
4.0 ... 7.5 kW
(5.0 ... 10.0 hp)
25.5 mm
(1.0 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch
C
11.0 ... 18.5 kW
(14.0 ... 24.0 hp)
32.5 mm
(1.27 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch
D
22.0 ... 30.0 kW
(29.0 ... 40.0 hp)
40.5 mm
(1.59 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch / Hummel
E
37.0 ... 45.0 kW
(50.0 ... 60.0 hp)
50.5 mm
(1.98 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch / Hummel
F
55.0 ... 90.0 kW
(73.0 ... 120.0 hp)
63.5 mm
(2.5 inches)
20.5 mm
(0.80 inches)
Schlemmer / Pflitsch / Hummel / Lappkabel
Содержание SINAMICS G120P