Technical data
10.2 Performance ratings Power Module
Converter with the control units CU240D-2
312
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Feature
Specification
Temperature sensor
•
PTC: Short-circuit monitoring < 22
Ω, switching threshold: 1650
Ω
•
KTY84: Short-circuit monitoring < 50
Ω, Short
-circuit monitoring: >
2120 Ω
•
Pt1000: Short-circuit monitoring < 603
Ω, Short
-circuit monitoring: >
2120 Ω
•
Temperature sensor with dry contact
Fail-safe input
•
DI 4 and DI 5 form the fail-safe digital input.
•
Maximum input voltage 30 V, 5.5 mA
•
Response time:
–
Typical: 5 ms + debounce time p9651
–
Typical, if debounce time = 0: 6 ms
–
Worst-case scenario: 15 ms + debounce time
–
Worst case, if debounce time = 0: 16 ms
•
You will find the extended function data in the "Safety Integrated"
Function Manual.
PFH
5 × 10E-8
Probability of failure of the fail-safe functions (Probability of Failure per
Hour)
USB interface
Mini-B (not available on the push-pull variants of the control unit)
10.2
Performance ratings Power Module
SINAMICS G120 D performance ratings
Table 10- 2 Power Module performance ratings
Feature
Specification
Line voltage & power
ranges
3 AC 380 V … 500 V ± 10 %
High Overload: 0.75 kW … 7.5 kW (1.0 hp … 10.0 hp)
Line specification
Relative short-circuit voltage of a transformer u
k
≤ 1%
The specification only refers to the total instantaneous regenerative feed-
back, however not to the total connected power of all of the power mod-
ules connected to the same transformer.
Output voltage
3 AC 0 V … line volage × 0.87 (max.)
Input frequency
47 Hz … 63 Hz
Output frequency
0 Hz … 240 Hz
cos
φ
1.05
Converter efficiency
95 % … 97 %
Overload capability (HO) 2 x Nominal output current for 3 seconds followed by 1.5 x Nominal output
current for 57 seconds every 300 seconds
Inrush current
Less than rated input current