Backing up data and series commissioning
7.3 Saving settings and transferring them using an operator panel
Converter with the control units CU240D-2
252
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
7.3
Saving settings and transferring them using an operator panel
Requirement
When the power supply is switched on, you can transfer the inverter settings to the IOP or
vice versa, transfer the IOP data to the inverter.
Inverter → IOP
-2
Procedure
1.
Connect the operator panel to the inverter.
2.
Start data transfer in the menu "UP/DOWNLOAD" -
"Drive to panel".
You have backed up the settings to the IOP-2.
❒
IOP-
2 → Inverter
Procedure
1.
Connect the operator panel to the inverter.
2.
Start data transfer in the menu "UP/DOWNLOAD" -
"Panel to drive".
3.
Switch off the inverter power supply.
4.
Wait until all LEDs on the inverter are dark. Now
switch on the inverter power supply again. Your
settings only become effective after this power-on
reset.
You have transferred the settings to the inverter.
❒