Advanced commissioning
6.4 Drive control via PROFIBUS or PROFINET
Converter with the control units CU240D-2
116
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Abbreviation
Explanation
Abbreviation
Explanation
NIST_A_GLATT Smoothed actual speed
value
WARN_CODE Alarm code
IAIST_GLATT
Smoothed current actual
value
MELD_NAMUR Message according to the VIK-
NAMUR definition
Interconnection of the process data
Figure 6-9
Interconnection of the send data
In the inverter, the send data are available in the "Word" format (p2051) - and in the "Double
word" format (p2061). If you set a specific telegram, or you change the telegram, then the
inverter automatically interconnects parameters p2051 and p2061 with the appropriate
signals.
Figure 6-10 Interconnection of the receive data
The inverter saves the receive data in the "Word" format (r2050), in the "Double word" format
(r2060) and bit by bit (r2090 …r2093). If you set a specific telegram, or you change the