SIMPRO-100
ASCII Serial Port Operation
6
PRIM-2400C
89
Table 6.4
SIMPRO-100 Serial Port Command
Summary
The serial port command explanations that follow
in the Command Explanations subsection are in
alphabetical order.
6.8
Command
Explanations
Each command explanation lists:
•
The command
•
The serial port access levels where the
command is available, in parentheses
•
An explanation of the command use or
response
For example, you can execute the HELP
command, below, from serial port Access Level 1
or 2.
6.8.1
HELP
(Level 1 or 2)
Use the HELP command to display the available
serial port commands. For more details regarding
a particular command, type HELP CMD, where
CMD is the name of the command you are
interested in.
6.8.2
ACC & 2AC
(Go to Access
Level 1 or 2)
The ACC and 2AC commands provide entry to
the multiple access levels. Different commands
are available at the different access levels as
shown in Table 6.4. Commands ACC and 2AC
are explained together because they operate
similarly.
•
ACC moves from Access Level 2 to Access
Level 1
•
2AC moves from Access Level 1 to Access
Level 2
See Section 6.8.27, page 93 for more information
on passwords. The factory default password for
Access Level 2 is 100.
The relay closes the ALARM b-contact for one
second after a successful Level 2 access. If you
make three incorrect password guesses, access
is denied and the ALARM contact closes for one
second.
Event Analysis Commands
1
EVENT
View event reports
1
HISTORY
View event summaries/
histories
2
HISTORY R Reset event history data
1
SER
View sequential events
recorder data
2
SER R
Reset sequential events
recorder data
1
TARGET
Display relay element status
1
TARGET R Reset target LEDs
1
TRIGGER
Trigger an event report
Motor Data Commands
1
LDP
Display load profile data
1
LDP D
Display load profile buffer
size
2
LDP R
Reset load profile data
1
MOTOR
Display motor statistics
2
MOTOR R
Reset motor statistics
1
MSR
Display motor start reports
1
MSR F
Display the format of a motor
start report
1
MST
Display motor start trend
data
2
MST R
Reset motor start trend data
2
RLP
Reset learned motor
parameters
Relay Setting Commands
1
SHOW
Show/view relay settings
2
SET
Enter/change relay settings
Relay Output Control Commands
2
ANALOG
Test analog output
2
CON
Control remote bit
2
PUL
Pulse output contact
2
STOP
Stop motor
2
STR
Start motor
Access
Level
Serial Port
Command
Command Description Page
Содержание SIMPRO-100
Страница 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Страница 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Страница 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Страница 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Страница 50: ...4 Settings Calculation SIMPRO 100 48 PRIM 2400C Figure 4 2 Generic Thermal Limit Curves Cold Motor ...
Страница 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Страница 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Страница 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Страница 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Страница 147: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 145 Figure B 3 Display Message Variables ...
Страница 157: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 155 Figure B 16 Overvoltage Element Logic ...
Страница 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Страница 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Страница 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Страница 239: ......