6.5.3
Connecting temperature monitoring for the stator winding
The stator winding is monitored for thermal loading by temperature sensors embedded in the
stator winding.
The connecting cables of the temperature sensors are routed to the main or auxiliary terminal
box, depending on the version. The connection and assignment of the terminals is specified
in the circuit diagram.
WARNING
Hazard due to electric shock
The installation of the temperature sensors for the winding monitoring with respect to the
winding is implemented according to the requirements for basic insulation. The temperature
sensor connections are located in terminal boxes, safe to touch, and have no protective
separation. This is the reason that in the case of a fault, a hazardous voltage can be present
at the measuring sensor cable. When touched, this can result in death, severe bodily injury
and material damage.
● When connecting the temperature sensor to external temperature monitoring devices,
when required, apply additional measures to fully comply with the requirements set out in
IEC 60664-1 or IEC 61800-5-1 "Hazard due to electric shock”.
6.5.4
Terminating the connection work (auxiliary circuit)
1. Before closing the auxiliary terminal box, please check that:
– The cables are connected in accordance with the terminal diagram.
– The cables are freely arranged so that they cannot come into contact with the machine,
and the cable insulation cannot be damaged.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– The cable glands are firmly tightened, are suitable with respect to the degree of
protection, type of cable routing, permissible cable diameter, etc., and have been
mounted in full compliance with specifications and regulations
– The threads in the connection plate are sealed using cable and conductor entries, thread
adapters or sealing plugs that achieve the respective degree of protection.
– Unused cable entries are sealed. The sealing elements are firmly screwed in, and can
only be released using a tool.
– All of the seals/gaskets and sealing surfaces of the terminal box are in good condition
– The screws of all of the screw clamps are fully tightened, even if they are not being used.
2. Close the auxiliary terminal box using the cover supplied for this purpose. See section
"Tightening torques for screw and bolt connections (Page 139)" for the tightening torque of
the fixing bolts for the cover.
Electrical connection
6.5 Connecting the auxiliary circuits
SIMOTICS TN Series N-compact 1LL8
80
Operating Instructions 11/2018
Содержание SIMOTICS TN 1LL8
Страница 2: ...15 11 2018 10 24 V17 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LL8 12 Operating Instructions 11 2018 ...
Страница 26: ...Description SIMOTICS TN Series N compact 1LL8 26 Operating Instructions 11 2018 ...
Страница 62: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LL8 62 Operating Instructions 11 2018 ...
Страница 98: ...Operation 8 9 faults SIMOTICS TN Series N compact 1LL8 98 Operating Instructions 11 2018 ...
Страница 132: ...Spare parts 10 14 Terminal box 1XB9600 SIMOTICS TN Series N compact 1LL8 132 Operating Instructions 11 2018 ...
Страница 136: ...Disposal 11 5 Disposal of components SIMOTICS TN Series N compact 1LL8 136 Operating Instructions 11 2018 ...
Страница 138: ...Service and Support SIMOTICS TN Series N compact 1LL8 138 Operating Instructions 11 2018 ...
Страница 142: ...Quality documents SIMOTICS TN Series N compact 1LL8 142 Operating Instructions 11 2018 ...
Страница 147: ......