Connecting
12.2010
38
ENGLISH
Siemens AG 6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
6.6
Terminal assignment, connectors
WARNING
If the unit is incorrectly connected, this can result in damage or destruction.
The power cable or busbars must be mechanically fixed outside the unit.
Power unit
Terminal type:
600 A / 1000 A / 1200 A units
Through hole for M10 (Cu - busbar 3x25)
2000 A units
Through hole for M10 (Cu - busbar 5x40)
The units are designed for a permanent line supply connection in accordance with DIN VDE 0160, Section
6.5.2.1.
Protective conductor connection: Minimum cross-section 10 mm
2
. (Connection option, see Chapter 5.1)
The connection cross-sections should be determined according to the applicable regulations -
e.g. DIN VDE 100 Part 523, DIN VDE 0276 Part 1000.
The connection lengths should be determined according to the diagram in Chapter 6 – Connecting.
Function Terminal
Connection
values/Comments
Armature power input
Protective conductor PE
Armature circuit-motor connection
1U1
1V1
1W1
1C1 (1D1)
1D1 (1C1)
see Technical data, Chapter 3.2
Pre-charging, main contactor / circuit breaker
Terminal strip WAGO 264-105
Conductor cross section
max. 2.5 mm
2
AWG max.
12
Stripped length
8 - 9 mm
Function Connection
Terminal
X_SCHÜTZ
Connection values/Comments
Power connection,
pre-charging
1
2
3
2U1
2V1
2W1
Cable cross-section 1.5 mm
2
Fuse protection 10 A (see Chapter 6.4)
Connection values the same as for the power unit
SIMOREG CCP (see above)
Control circuit for
main contactor /
circuit breaker
4
5
Wiring, main contactor/circuit breaker
(see the recommended connection in Chapter 6.2)