12.2010
Description, technical data
Siemens AG 6RX1700-0DD74
ENGLISH
17
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
3.2 Technical
data
Order No.
6RA70...
..85-6FC00-0
..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0
Rated voltage
460 V
(+15% / -20%)
460 V
(+15% / -20%)
690 V
(+10% / -20%)
460 V
(+15% / -20%)
690 V
(+10% / -20%)
Rated current
600 A
1200 A
1000 A
2000 A
2000 A
current range that can be
covered
to 600 A
to 1200 A
to 1000 A
to 2000 A
to 2000 A
Rated supply voltage
Electronics power supply
2 AC 380 V (-20 %) to 460 V (+15 %); In=1 A or
1 AC 190 V (-20 %) to 230 V (+15 %); In=2 A
Rated frequency
45 to 65 Hz
Power loss
100 W
Ambient temperature
Operation:
0 to 55 °C
storage, transport:
-25 to +70 °C
Installation altitude above sea
level
≤
2000 m without derating
> 2000 m with voltage derating *)
Environmental class
3K3 acc. to DIN IEC 60 721-3-3
Pollution degree
2 acc. to EN50178 **)
Degree of protection
IP00 acc. to DIN EN 60529
Dimensions (W x H x D)
780 x 406 x 500 mm, dimension drawing, see Chapter 5.1
Weight (approx.)
35 kg
35 kg
45 kg
55 kg
75 kg
*) Voltage derating as a function of installation altitude:
When supplying the electronics with voltages of 460 VAC phase to phase (maximum 300 VAC with respect
to ground) operation is permitted up to 4500 m. A maximum of 400 VAC phase to phase (maximum 230 V
AC with respect to ground) is permitted up to 5000 m. At higher altitudes or a higher voltage, there is no
longer "safe electrical separation" - but only basic insulation.
**) Definition, pollution degree 2:
Normally, only non-conductive pollution occurs. However, occasionally conductive pollution can be expected
for a short period of time if the electronic equipment is not operational.
Wait time, recovery time:
Each time that the line supply voltage is connected (e.g. via a line contactor):
The quenching capacitors in the unit are charged.
The wait time until the SIMOREG CCP is ready, is
approx. 3 s
After
one
quenching operation:
The time until the SIMOREG CCP is ready again depends on the operations during the quenching
process and immediately afterwards.
The quenching capacitors in the SIMOREG CCP are again recharged to the required value,
duration
approx. 10 s
.
The chopper resistors, which convert the energy into heat when the armature current is reduced,
require a cooling time.
This is calculated using a software algorithm, and depending on the energy that is dissipated
during the quenching operation, is up to
approx. 20 min
.