7.4 Line filters for I/R and UI modules
7-237
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Table 7-16
Assigning the basic line filters to the I/R modules
I/RF module
16/21 kW
I/RF module
36/47 kW
I/RF module
55/71 kW
Filter
components
Line filter
16 kW
Line filter
36 kW
Line filter
55 kW
Rated AC current
36 A
65 A
105 A
Supply voltage
3–ph. 380 V AC – 10% ... 3 –ph. 480 V + 10%/–15% < 1 min) (TN line supply)
1)
; 47 ... 63
Hz
Order number
6SL3000–
0BE21–6DA
6SL3000–
0BE23–6DA
6SL3000–
0BE25–5DA
Mounting position
Wall or base/floor mounting, refer to Fig. 7-14
Dimensions (W x H x D),
approx.
50x429x226
75x433x226
100x466x226
Module width
Refer to dimension drawings, Chapter 12
Weight, filter
5 kg
6.5 kg
11.5 kg
Power loss
16 W
28 W
41 W
Connection
10 mm
2
/1.5 Nm
PE, M6 studs
/3 Nm
2)
35 mm
2
PE, M6 studs
/3 Nm
2)
50 mm
2
PE, M6 studs
/3 Nm
2)
Terminals
Line supply connection
(line)
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
Terminals
Load connection (load)
L1’, L2’, L3’, PE
L1’, L2’, L3’, PE
L1’, L2’, L3’, PE
I
rated
fuse
4)
35 A
80 A
125 A
Compatibility, residual cur-
rent protective devices
The discharge current is limited to approx. 110 mA in conjunction with a universally cur-
rent sensitive residual current protective device and Siemens cables and the 150 m cable.
Permissible
ambient temperature
Operation
[
°
C]
Storage/transport
[
°
C]
0 ... +40; m55 at 0.6
•
P
rated
of the l/R module
–25 ... +70
Cooler
Natural ventilation
Degree of protection to EN
60529 (IEC 60529)
IP20
DIN EN 61800-3 (IEC
61800-3)/VDE 0160-103 ra-
dio interference suppres-
sion
Limit value Class C 2
1) The permissible supply voltage of the system depends on the infeed module used.
2) For ring terminal end in accordance with DIN 46234
3) Being prepared
4) The fuse used must have this rated current. Recommendations for the fuses, refer to Table 7-6.
7 Line Supply Connection