Analog inputs
6-529
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.6.1
Basic setting of the analog inputs
The following functions can be assigned to analog input 1 and 2 of a
drive using the appropriate parameterization:
Table 6-51
Parameters for the function of the analog inputs
Analog
input
Parameters
1
2
No.
Description
Min.
Stan-
dard
Max.
Units
Ef-
fec-
tive
0607
Analog setpoint, terminal 56.x/14.x
0
1
2
–
Im-
medi-
ately
56 x
14 x
–
The parameter defines whether and how the analog setpoint is used at this analog
input.
= 0
––> off
= 1
––> n
set
/M
set
mode (refer to Note)
= 2
Velocity override (refer under the index entry ”Override”)
0612
Analog setpoint, terminal 24.x/20.x
0
0
2
–
Im-
medi-
ately
–
24 x
20 x
The parameter defines whether and how the analog setpoint is used at this analog
input.
= 0
––> off
= 1
––> n
set
/M
set
mode (refer to Note)
= 2
––> M
red
mode
Note:
x:
Space retainer for drive A or B
n
set
/M
set
mode:
It is always possible to toggle between n
set
and M
set
mode using the ”open–loop torque controlled
operation” input signal (refer to Chapter 6.4.2).
0 signal:
n
set
mode
1 signal:
M
set
mode
Input terminal I3.x is assigned, as standard, to the ”open–loop torque controlled mode” signal.
When toggling between n
set
and M
set
mode, it should be noted, that a setpoint, which may be present
at the terminals, becomes immediately effective in the other operating mode.
Parameter
overview
6 Description of the Functions
01.99
! not 611ue !