Tables, data records
3.6 EtherNet/IP data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
329
3.6.7
Measurement object
The Measurement object supplies the latest measurements of quantities such as current,
voltage, output, cos phi, etc. of the SIMOCODE pro V EtherNet/IP device.
●
Class code: 0x0097
●
Class attributes: 0
●
Number of instances: 1
●
Object length: 240 bytes
Table 3- 95 General services for the Measurement object
Service code
Available service
Service designation
Description
Class
Instance
0x01
No
Yes
Get_Attributes_All
Supplies contents of all attributes
0x0E
No
Yes
Get_Attribute_Single
Supplies contents of one attribute
Table 3- 96 Attributes of instance 1 for the Measurement object
Attribute ID Access
Designation
Data type
Range
Unit
1
Get
Thermal motor model
INT
See
2)
2
Get
Phase unbalance
SINT
0 .. 127
1 %
3
Get
Cos φ
SINT
0 .. 127
1 %
4..8
Get
Reserved
INT[5]
9
Get
Max. current I_max
INT
0 .. 32767
1 % / I
s
10
Get
Current I_L1
INT
0 .. 32767
1 % / I
s
11
Get
Current I_L2
INT
0 .. 32767
1 % / I
s
12
Get
Current I_L3
INT
0 .. 32767
1 % / I
s
13
Get
Last trip current
INT
0 .. 32767
1 % / I
s
14
Get
Time to trip
DINT
100 ms
6)
15
Get
Recovery time
DINT
100 ms
16
Get
Voltage U_L1
INT
0 .. 32767
1 V
17
Get
Voltage U_L2
INT
0 .. 32767
1 V
18
Get
Voltage U_L3
INT
0 .. 32767
1 V
19
Get
AM1 - output
INT
0 .. 32767
See
1)
20
Get
AM1 - input
INT
0 .. 32767
21
Get
AM1 - input 2
INT
0 .. 32767
22
Get
Reserved
INT
23
Get
TM1 - temperature
INT
0 .. 32767
1 K see
3)
24
Get
TM1 - temperature 1
INT
0 .. 32767
1 K see
3)
25
Get
TM1 - temperature 2
INT
0 .. 32767
1 K see
3)
26
Get
TM1 - temperature 3
INT
0 .. 32767
1 K see
3)
27
Get
Reserved
INT