Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
175
3.3.2.11
Data record 130 - Basic device parameters 1
Table 3- 33 Data record 130 - Basic device parameters 1
Byte.Bit Designation (PRM group)
Type Range
Unit
Default Note
Information
0.0
Coordination (byte[4]
Byte
BU0 BU1 BU2(+)
4.0
Device class
Byte 5, 7, 9
5 = BU1
7 = BU0
9 = BU2(+)
BU0 BU1 BU2(+)
5.0
Thermistor
Bit
0, 1
1 = active; thermistor in
the BU
BU0 BU1 BU2(+)
(+)5.1
Reserved
Bit[5]
5.6
Multifunction module (MM). Bit
0, 1
BU0
5.7
Initialization module (InM)
Bit
0, 1
BU0 BU2(+)
6.0
Operator panel (OP)
Bit
0, 1
BU0 BU1 BU2(+)
6.1
Analog module 1 (AM1)
Bit
0, 1
BU2(+)
6.2
Temperature
module 1 (TM1)
Bit
0, 1
BU0 BU2(+)
6.3
3UF7500 ground-fault
module for 3UL22 residual
current transformer
Bit
0, 1
BU2(+)
6.4
Digital module 1 (DM1)
Bit[2] 0 - 3
0 = no digital module
1 = monostable
2 = bistable
3 = special type (see 3.4)
BU0 BU2(+)
6.6
Digital module 2 (DM2)
Bit[2] 0 - 2
BU2(+)
7.0
Operator panel with
display (OPD)
Bit
0, 1
BU2(+)
7.1
3UF7510 ground-fault
module for 3UL23 residual
current transformer
Bit
0, 1
BU0 BU2(+)
7.4
DM1 - Special type
Bit[2] 0, 1
0 = DM-FL
1 = DM-FP
BU2(+)
7.6
Reserved
Bit[2]
8.0
Current measuring (IM)
Bit[7] 0 - 5
IM / UM:
0 = no current
measurement
1 = 0.3 A - 3 A
2 = 2.4 A - 25 A
3 = 10 A - 100 A
4 = 20 A - 200 A
5 = 63 A - 630 A
UM+:
9 = 0.3 A - 4 A
10 = 3 A - 40 A
11 = 10 A - 115 A
12 = 20 - 200 A
13 = 63 - 630 A
BU0 BU1 BU2(+)