Upgrading Existing Series 500 Installations
D-13
TI545/TI555 System Manual
Table D-1
Base Numbers
Thumbwheel
Number
Base Number
Thumbwheel
Number
Base Number
Do Not Use
0*
8
8
1
1
9
9
2
2
10
10
3
3
11
11
4
4
12
12
5
5
13
13
6
6
14
14
7
7
15
15
Notes:
*
Base 0 is reserved on the model TI545/TI555 controller for local base
assignment. Therefore, do not select number 0 on the Series 500 RBC.
The display at the top of the module (refer to Table D-2) indicates the status
of the Series 500 RBC. Status is displayed in integer format; see Table D-2
for definitions of the displays.
Table D-2
Series 500 RBC LED Messages
Display
Definitions
0
RBC Good
1
Self Diagnostics Failure
2
Module Mismatch
3
I/O Communication Time Out
4
RAM Parity Error
5
Not used
6
Not used
7
Communication Good, Not Configured
8
Watchdog Timer Expired
Series 500 RBC
LED Display