STARTUP / TROUBLESHOOTING
5-3
Hardware and Installation User Manual
6.
Using the programming device, enter the I/O configuration.
7.
Enter the RLL program. See the SIMATIC TI505 Programming
Reference manual for information about designing your RLL program.
8.
Use the programming device to JOG motors, solenoids, or other
positioning devices one at a time to establish correct rotation or
position.
After all the steps are performed and verified, place the PLC in the RUN mode.
If you turn ON the L-memory MEMORY PROTECT dipswitch, your RLL
program cannot be changed by a programming device that is connected to the
PLC through one of the communication ports.
NOTE
The MEMORY PROTECT dipswitch does not prevent forcing
I/O, changing variable memory, or switching the PLC from
PROGRAM to RUN mode. These actions may be made by a
programming device connected to the PLC, or a special function
I/O module designed for this type of interface to the PLC, e.g., a
Network Interface Module. The RLL can also be changed
through a special function module, even when the memory
protection is enabled.
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com