Signal modules
5.1 SM500 signal module
SIMATIC TDC hardware
108
System Manual, 08/2017, A5E01114865-AL
5.1.7
Incremental encoder input settings
Depending on the type of encoder used (15 V or 5 V encoder), switches S1 and S2 must be
set on the module corresponding to the following table.
Each track (A/VW, B/RW, N/-) of a channel has a switch that can be used to set the
appropriate encoder type:
●
Switch open (OFF):
15 V encoder, switching threshold 7 V
●
Switch closed (ON):
5 V encoder, switching threshold 0 V
All tracks (A/VW, B/RW, N/-) of a channel must have the same switch setting for operation.
Note
If you are using a TTL incremental encoder you must note that you cannot switch the control
input to TTL signals. The control input only reacts to a HTL level.
Settings for encoder type with switches S1 and S2
Table 5- 4
Switch settings for 5 V and 15 V encoders
Channel
Track
Switches
15 V encoder
5 V encoder
Encoder 1
A/VW
S1, 1
OFF
ON
B/RW
S1, 2
N/-
S1, 3
Encoder 2
A/VW
S1, 4
OFF
ON
B/RW
S1, 5
N/-
S1, 6
Encoder 3
A/VW
S2, 1
OFF
ON
B/RW
S2, 2
N/-
S2, 3
Encoder 4
A/VW
S2, 4
OFF
ON
B/RW
S2, 5
N/-
S2, 6