![Siemens SIMATIC S7-CPs Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/siemens/simatic-s7-cps/simatic-s7-cps_manual_382089012.webp)
2 Requirements for Use
B
−
12
CP 443-1 for Industrial Ethernet / Manual Part B
Release 07/2010
C79000-G8976-C223
−
06
Table 2-1
CPU data relevant to use of the CP
CPU
as of firmware version
Order number of
the CPU:
6ES7...
CPU
Multiprocessing possible
Order number of
the CPU:
6ES7...
CPU
Max. number of CPs
Order number of
the CPU:
6ES7...
CPU
CPU resources for
SEND-/RECEIVE jobs
1)
Order number of
the CPU:
6ES7...
LOCK/UNLOCK
PROFINET IO
4)
CPU 416-3 PN/DP
..416
−
3ER05
−
0AB0
V5.1
+
2)
14
64
+
+
CPU 416F
−
3 PN/DP
..416
−
3FR05
−
0AB0
as of
V5.1
+
2)
14
64
+
+
CPU 417-4
..417
−
4XL04
−
0AB0
V4.1
+
2)
14
64
+
−
CPU 417-4
..417
−
4XT05
−
0AB0
as of
V5.1
+
2)
14
64
+
+
CPU 412-3H
3)
..412-3HJ14-0AB0
V4.5
+
2)
14
64
+
−
CPU 414H
3)
..414-4HM14-0AB0
V4.5
+
2)
14
64
+
−
CPU 414H
3) 5)
..414
−
4HJ04
−
0AB0
V4.0
+
2)
14
64
+
−
CPU 417H
3)
..414-4HR14-0AB0
V4.5
+
2)
14
64
+
−
CPU 417H
3)
..417
−
4HT14
−
0AB0
V4.5
+
2)
14
64
+
−
CPU 417H
3) 5)
..417
−
4HL04
−
0AB0
V4.0
+
2)
14
64
+
−
Legend:
+ => The feature is supported / the specified mode is possible
=> the feature is
not
supported / the specified the mode is
not
possible
1)
The calculation of the maximum number of SEND/RECEIVE calls that can be used simultaneously per CP
is described in Section 5.3.2.
2)
When using the CP as a PROFINET IO controller, multiprocessor mode is not supported, in other words,
only the process image of the assigned CPU can be distributed via the CP (Note: this does not affect
communication protocols running at the same time in multiprocessor mode).
3)
When operating with H-CPUs, the SSEND / SRECV mode on the SEND/RECV interface is not supported.
H
−
CPUs do not support PROFINET.
4)
The PROFINET IO mode shared device requires a CPU as of Version V5.3.
5)
When operating these H CPUs, the CP must be configured as module type CP 443
−
1 EX11.
2.3
Configuration
The following version of STEP 7 is required:
Table 2-2
STEP 7 version
CP 443-1 functionality
as of V5.4 + Service Pack 4
The full functionality as described in this document can be used.