Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
272
System Manual, 03/2012, A5E00267695-11
16.2.5
Failure and replacement of a synchronization module or fiber-optic cable
In this section, you will see three different error scenarios:
●
Failure of a synchronization module or fiber-optic cable
●
Successive failure of both synchronization modules or fiber-optic cables
●
Simultaneous failure of both synchronization modules or fiber-optic cables
The CPU indicates by means of LEDs and diagnostics whether the lower or upper redundant
link has failed. After the defective parts (fiber-optic cable or synchronization module) have
been replaced, LEDs IFM1F and IFM2F must go out.
Starting situation
Failure
How does the system react?
Failure of a fiber-optic cable or synchronization
module:
The S7-400H is in redundant system mode and a
fiber-optic cable or synchronization module fails.
See also chapter Synchronization modules for
The master CPU reports the event in the
diagnostic buffer and with OB 72 of OB 82.
The reserve CPU changes to ERROR-
SEARCH mode for some minutes. If the error
is eliminated during this time, the reserve
CPU switches to redundant system mode,
otherwise it switches to STOP.
The LED Link1 OK or Link2 OK on the
synchronization module is lit.
Procedure
Follow the steps below to replace a synchronization module or fiber-optic cable:
Step
What has to be done?
How does the system react?
1
First, check the fiber-optic cable.
–
2
Start the reserve CPU (for example, STOP-
RUN or Start using the programming device).
The following responses are possible:
1.
CPU changes to RUN mode.
2.
CPU changes to STOP mode. In this
case continue at step 3.
3
Remove the faulty synchronization module
from the reserve CPU.
–
4
Insert the new synchronization module in the
reserve CPU.
–
5
Plug in the fiber-optic cable connections of
the synchronization modules.
The LED Link1 OK or Link2 OK on the
synchronization module goes out.
Both CPUs report the event in the
diagnostic buffer
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...