Table 5-11
Representation of analog values in the voltage measuring ranges 1 to 5 V and 0 to 10 V
System
Voltage measuring range
Dec.
Hex.
1 to 5 V
0 to 10 V
118,515 % 32767
7FFF
5.741 V
11.852 V
Overflow
117,593 % 32512
7F00
117,589 % 32511
7EFF
5.704 V
11.759 V
Overshoot range
27649
6C01
100,000 % 27648
6C00
5 V
10 V
Nominal range
75 % 20736
5100
3.75 V
7.5 V
0,003617 % 1
1
1 V + 144.7 µV
0 V + 361.7 µV
0 % 0
0
1 V
0 V
- 1
FFFF
Undershoot range
- 17,593 % - 4864
ED00
0.296 V
Negative values are not
supported
Wire break
≤-17,596 % 32767
7FFF
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
173