Analog value processing
C.1 Conversion method
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
195
Smoothing
The individual measured values are smoothed by filtering. The smoothing can be set in 4
levels and channel-selective in STEP 7 (TIA Portal).
Smoothing time = Smoothing (k) x configured integration time
The following figure shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing. This is valid for all signal changes at
the analog input.
①
None (smoothing = 1 x integration time)
②
Weak (smoothing = 4 x integration time) *
③
Medium (smoothing = 16 x integration time) *
④
Strong (smoothing = 32 x integration time) *
* The smoothing time can increase by 1 x integration time.
Figure C-5 Smoothing time depending on the set smoothing level
The following table shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing and the set interference frequency
suppression.
Table C- 2 Smoothing time depending on the set smoothing level and interference frequency suppression
Selection of the smoothing
(mean value generation from scan values)
Interference frequency suppression/smoothing time
400 Hz
60 Hz
50 Hz
10 Hz
None
2.5 ms
16.6 ms
20 ms
100 ms
Weak
10 ms
66.4 ms
80 ms
400 ms
Medium
40 ms
265.6 ms
320 ms
1600 ms
Strong
80 ms
531.2 ms
640 ms
3200 ms