Expansion of Basic System with External I/Os
S5-95F
5.5
Connection of Failsafe I/O Modules
If the failsafe onboard inputs and outputs are not sufficient for your application, you can expand the
S5-95F with the following I/O modules:
•
Failsafe input module DI 431-8FA..
•
Failsafe output module DQ 450-8FA..
Please note that the reaction times change when you use I/O modules.
You can use the I/O modules DI 431-8FA.. and DQ 450-8FA.. both in single-channel and two-
channel operation. For safety functions, you must always use the modules in two-channel operation
and parameterize them with COM 95F.
No matter whether you operate the above-mentioned modules in single or two-channel operation,
the modules are subject to a high-grade function test.
Note
Make sure that the load voltage for all failsafe external I/O modules is connected. If the
load voltage is not connected, the S5-95F reacts with a fault message and with the
safety reaction programmed in DB1.
System Reaction to I/O Faults
The reaction to an I/O fault depends on whether you use the I/O modules in single or two-channel
operation.
When you use the I/O modules in
two-channel operation, the S5-95F reacts as follows:
•
The yellow fault LED is set
•
The fault is entered into the system event DB 254
•
Error OB 37 is processed
•
System reaction as programmed in DB1
When you use the I/O modules in
single-channel operation, the S5-95F reacts as follows:
•
The yellow fault LED is set
•
The fault is entered into the system event DB 254
•
Error OB 37 is processed
•
The user program is executed (no further system reaction)