Upkeep and maintenance
6.3 Firmware update via WBM or CLI not possible
SCALANCE W774-1 /W734-1
Operating Instructions, 07/2020, C79000-G8976-C325-14
53
Solution
You can then also assign firmware to a SCALANCE W using TFTP.
Follow the steps below to load new firmware using TFTP:
1.
Turn off the power to the device.
2.
Now press the Reset button and reconnect the power to the device while holding down
the button.
3.
Hold down the button until the red fault LED (F) starts to flash after approximately 2
seconds.
4.
Now release the button. The bootloader waits in this state for a new firmware file that
you can download by TFTP.
5.
Connect a PC to the SCALANCE W over the Ethernet interface.
6.
Assign an IP address to the SCALANCE W with the SINEC PNI.
7.
Open a DOS box and change to the directory where the file with the new firmware is
located and then execute the command "tftp -i <ip address> PUT <firmware>". As an
alternative, you can use a different TFTP client.
8.
Close the cover to ensure that the device is closed and water and dust proof.
Note
Use of CLI and TFTP in Windows 10
If you want to access the CLI or TFTP in Windows 10, make sure that the relevant
functions are enabled in Windows 10.
Result
The firmware is transferred to the device.
Note
Please note that the transfer of the firmware can take several minutes. During the
transmission, the red error LED (F) flashes.
Once the firmware has been transferred completely to the device, the device is restarted
automatically.