Certification
6.2 EMC and Environmental Type Tests
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1510 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal ports
± 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV
4
Signal ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports
10 V
3
100 A/m, continuous
1000 A/m for 1 s
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal ports
IEC 61000-4-16
Mains Frequency
Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports
2 kV (Failsafe Relay output)
DC Power Ports
1.5 kV
IEC 60255-5
Dielectric Strength
AC Power Ports
2 kV
RUGGEDCOM RX1510
Installation Manual, 04/2021, C79000-G8976-1055-20
53