Certification
6.2 EMC and Environmental Type Tests
EMC Type Test for IEC 61850-3
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal ports
± 4 kV @ 2.5 kHz
Note
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV
4
Signal ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports
10 V
3
100 A/m, continuous
1000 A/m for 1 s
Note
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal ports
IEC 61000-4-16
Mains Frequency
Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports
2 kV (Failsafe Relay output)
DC Power Ports
1.5 kV
Dielectric Strength
AC Power Ports
2 kV
Signal ports
5 kV (Failsafe Relay output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
Siemens-specified severity levels.
46
RUGGEDCOM RX1501
Installation Manual, 10/2021, C79000-G8976-1054-21