Product Information/Installation Instructions CP 5613 A2, CP 5614 A2
Product Information/Installation Instructions CP 5613 A2, CP 5614 A2
A5E00779184
37
4
FAQ (Frequently Asked Questions)
Overview
In this chapter, you will find the answers to typical questions (
F
requently
A
sked
Q
uestions) about product properties.
What do the LEDs mean?
Green and yellow LED
Meaning
green lit
DP master: Indicates token rotation (in other
words, normal operation)
green off
DP master: Incorrect bus parameters, defective
bus, or CP not in operation
green flashing at one second
intervals
DP master: Errors in database
green and yellow flashing
alternately
Module being addressed by the diagnostic tool to
check the installation.
yellow lit
DP slave: Indicates polling by the DP master (in
other words, normal operation)
yellow off
DP slave: Port not being addressed.
green flashing fast
Module not started (normal state after reset).
green and yellow flashing
synchronously
Exception state (error in firmware)
one of the two LEDs is on
the other flashes fast.
Error initializing the module.
Does the module have the CE mark?
Yes, refer to the Appendix, page 43.
Which approvals do the CP 5613 A2 and CP 5614 A2 have for USA and Canada?
●
cULus — Combined UL and CSA approval
●
FCC
Class
B
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com