Configuration
3.4 Other options when configuring a CP 243-1
CP 243-1
86
Operating Instructions, 03/2012, C79000-G8976-C244-02
Parameter
Description
Example
Number of bytes
Number of bytes (0 to max. of 10240
with CPU226XM) that can be written to
the DB or read from the DB.
00|W|5354|<DB_start_address>|<path/
_file name>|<server_address>|
<user_name>|<password>
Starting with address
<DB_start_address>, 5354 bytes are
read from the DB of the CPU and,
using <user_name> and <password>,
written to the file <path/file_name> on
the computer specified by
<server_address>.
DB start address
Start address starting at which the DB
block is be read from or written to.
The value range refers to the size of
the existing DB (depends on the CPU,
with CPU226XM between 0 and 10239)
00|R|5354|VB2308|<path/file_name>|<
server_address>|<user_name>|<passw
ord>
The file <path/file_name> is transferred
from the file system of the FTP server
addressed via the IP <server_address>
(stating <user_name> and
<password>) to the FTP client of the
CP 243-1. There, 5354 bytes from the
file are written to the DB of the CPU
starting at address VB2308.
Path/file name
Specification of the file from which/to
which data will read or written,
including the related path information.
The file name may contain up to 254
characters. The complete path
including file name must not exceed
1024 characters.
00|R|23|VB11|/flash:/dat/CPU10_VB11
_23.dat|
<server_address>|<user_name>|
<password>
The file
/flash:/dat/CPU10_VB11_23.dat is
transferred from the file system of the
FTP server addressed via the IP
<server_address> (stating
<user_name> and <password>) to the
CP 243-1. There, 23 bytes from the file
are written to the DB of the CPU
starting at address VB11.
Server address
Entry of the IP address at which the
FTP server can be accessed
00|R|23|VB11|/flash:/dat/CPU10_VB11
_23.dat| 192.168.162.65|<user_name>|
<password>
The file
/flash:/dat/CPU10_VB11_23.dat is
transferred from the file system of the
FTP server obtainable with the IP
192.168.162.65 (stating <user_name>
and <password>) to the CP 243-1.
There, 23 bytes from the file are written
to the DB of the CPU starting at
address VB11.
Содержание SIMATIC NET CP 243-1
Страница 6: ...Preface CP 243 1 6 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 10: ...Table of contents CP 243 1 10 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 104: ...Programming 4 5 ETHx_FTPC CP 243 1 104 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 118: ...Diagnostics 5 2 Error messages of the CP 243 1 CP 243 1 118 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 124: ...Certification CP 243 1 124 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 138: ...Sample program CP 243 1 138 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Страница 142: ...Index CP 243 1 142 Operating Instructions 03 2012 C79000 G8976 C244 02 ...