Configuration
3.20 Configuring data points
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
111
Format (memory
requirements)
Data point type
DNP3 object
group
[variation]
Direction
S7 data types
Operand area
CP
TIM
Floating-point num-
ber (32 bits)
Analog Input
30 [5]
in
Real
-
Q, M, DB
Analog Input Event
32 [5, 7]
in
Real
-
Q, M, DB
Analog Output Sta-
tus
4)
40 [3]
out
Real
-
Q, M, DB
Analog Output
41 [3]
out
Real
-
Q, M, DB
Analog Output
Event
4)
42 [5, 7]
out
Real
-
Q, M, DB
Floating-point num-
ber (64 bits)
Analog Input
30 [6]
in
LReal
-
Q, M, DB
Analog Input Event
32 [6, 8]
in
LReal
-
Q, M, DB
Analog Output
41 [4]
out
LReal
-
Q, M, DB
Analog Output
Event
4)
42 [6, 8]
out
LReal
-
Q, M, DB
Data block
(1...64 bytes)
5)
Octet String / Octet
String Output
110 [ - ]
in, out
5)
5)
DB
Octet String Event
5)
111 [ - ]
in, out
5)
5)
DB
1)
This object group can be configured in the data point editor of STEP 7 using the substitute object group 12.
2)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 20.
3)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 22.
4)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 41.
5)
With these data point types, contiguous memory areas up to a size of 64 bytes can be transferred. All S7 data types with
a size between 1 and 64 bytes are compatible.
Explanation of the table footnotes
1)
,
2)
,
3)
,
4)
: Configuring data points using substitute object
groups
The initial data point types of the following object groups can be configured using the
substitute object groups listed above:
●
10 [2]
●
11 [1, 2]
●
21 [1, 2, 5, 6]
●
23 [1, 2, 5, 6]
●
40 [1, 2, 3]
●
42 [1, 2, 4, 5, 6, 7, 8]
Use the specified substitute object group for the configuration.
Assign each data point on the master using the configurable data point index in STEP 7. The
data point of the station module is then assigned to the corresponding data point on the
master.
Example of configuring the data point Binary Output (10 [2])
The data point is configured as follows:
In the station module as Binary Command (12 [1])
On the master as Binary Output (10 [2])