5
Configuration
Process
5.2
STEP 7 configuration
42
Evaluating An Access Point Clients List
V1.0, Entry ID: 48946495
C
opyr
ight
Si
em
ens
AG
20
1
1
A
ll rig
h
ts
re
se
rve
d
No.
Action
Screens
3.
Configuring “F-FB162” (F_FB_RNG_4):
Up to four mobile panels can be configured
with F-FB162. Separate I/O parameters are
available for each mobile panel.
(MP1 = Mobile Panel 1, MP2 = Mobile Panel
2 etc.).
RNG_ID = Effective range ID
*1)
MP1_DATA = PAE Word 1
*2)
MP1_RNG = PAE Word 2
*2)
MP1_STAT = F_DB_STATES.
DBW0
*1)
The effective range ID is configured in the
“Device settings > Effective ranges” menu
option in WinCC flexible. Each effective range
has its own “ID number”.
(Effective ranges are not configured in the
standard configuration).
*2)
The addresses can be found in the
hardware configuration of the S7-300 station
on the IO device of the mobile panel under
the “
Mobile277Failsafe_IO
” module.
E_STOP =
*3)
GLOB_RD =
*3)
LOC_RD =
*3)
SHUTDOWN =
*3)
*3)
Depending on the situation in the plant,
different switch-off behaviors can be
configured
by these outputs.
An interconnection and an evaluation of the
outputs
must
be configured in the F-CPU,
otherwise there will be
no
switching off.
Note:
The outputs are
not
interconnected in the
standard configuration.