Connecting
3.3 Connecting the supply voltages
PDC100(F)
Equipment Manual, 03/2021, A5E50502703-AA
23
⑩
X5050:
Connection for external braking resis-
tor
MRES
Service button LED
⑪
Supply for power unit
PN
PROFINET status display LEDs
⑫
2-port switch
CHx
Input/output LEDs
⑬
Service button
PWR
Supply voltage LEDs
⑭
X4050:
Rotational speed acquisition (Hall
sensor, incremental encoder)
⑮
microSD memory card
Figure 3-2
Block diagram of the PDC100(F)
3.3
Connecting the supply voltages
Introduction
You connect the 24 V DC supply voltage for the PDC logic unit and the inputs/outputs to
terminal connectors X5060 (1L+ and 1M) and X4060 (2L+ and 2M).
Pins 3/4 (2L+) and Pins 1/2 (2M) of interface X4060 are electrically connected to one another.
If you connect the supply voltage to Pin 3 (2L+) and Pin 1 (2M), you can use terminals 4 (2L+)
and 2 (2M) to loop through the potential to Pins 3 (1L+) and 1 (1M) of interface X5060.
You connect the 24 V DC to 48 V DC supply voltage for the power unit to connector X5050
(4L+ and 4M).
Requirements
•
Only wire the connection plug when the supply voltage is turned off.
•
Observe the rules and regulations on operation described in the System Manual SIMATIC
MICRO-DRIVE Drive controller PDC
https://support.industry.siemens.com/cs/ww/en/view/109774126
).
•
Observe the rules and regulations described in section Product overview (Page 11).
Required tool
Screwdriver (recommended):
•
For double-level terminal connector, size 0.4 x 2.5 mm
•
For single-level terminal connector, size 0.6 x 3.5 mm