5.2
Module/channel parameters
Parameters of the DQ 32x24VDC/0.5A HA
You have the following setting options:
Table 5-1
Parameters and their default settings
Parameter
Value range
Default
Parameter re‐
assignment in
RUN
Efficiency range
Diagnostics,
Missing supply voltage L+
● Enabled
● Disabled
Enabled
Yes
Module
Diagnostics
Short-circuit to ground
● Enabled
● Disabled
Enabled
Yes
Channel
Channel activated
● Enabled
● Disabled
Enabled
Yes
Channel
Reaction to CPU STOP
● Shutdown
● Keep last value
● Output substitute value
Shutdown
Yes
Channel
Substitute value
1
● 0
● 1
0
Yes
Channel
Potential group
● Use potential group of the left
module
● Allow new potential group
Use potential
group of the left
module
No
Module
Double-wide terminal block
2
● Enabled
● Disabled
Disabled
No
Configuration
(HW Config)
1
Only applicable when the value "Output substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
2
I/O module on terminal block with potential distributor: Select the "Double-width terminal block" parameter in the hardware
properties for the I/O module.
Parameters
5.2 Module/channel parameters
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
18
Manual, 09/2018, A5E39265993-AA