Technical specifications
6.1 Technical specifications
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1)
29
Equipment Manual, 06/2020, A5E03551866-AF
Article number
6ES7134-6GD01-0BA1
Interrupts/diagnostics/status information
Diagnostics function
Yes
Alarms
•
Diagnostic alarm
Yes
•
Limit value alarm
No
Diagnostic messages
•
Monitoring the supply voltage
Yes
•
Wire-break
Yes; at 4 to 20 mA
•
Short-circuit
Yes; 2-wire mode: Short-circuit of the encoder
supply to ground or of an input to the encoder
supply
•
Group error
Yes
•
Overflow/underflow
Yes
Diagnostics indication LED
•
Monitoring of the supply voltage (PWR-
LED)
Yes; green LED
•
Channel status display
Yes; green LED
•
for channel diagnostics
No
•
for module diagnostics
Yes; green/red LED
Potential separation
Potential separation channels
•
between the channels
Yes; channel group-specific between 2-wire cur-
rent input group and 4-wire voltage input group
•
between the channels and backplane bus
Yes
•
between the channels and the power sup-
ply of the electronics
Yes; only for 4-wire transducer
Permissible potential difference
between the inputs (UCM)
10 V DC
Isolation
Isolation tested with
707 V DC (type test)
Ambient conditions
Ambient temperature during operation
•
horizontal installation, min.
-30 °C
•
horizontal installation, max.
60 °C
•
vertical installation, min.
-30 °C
•
vertical installation, max.
50 °C
Altitude during operation relating to sea level
•
Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2
000 m, see manual