4 IQ-SENSE
13-9
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
13.2
Control (PIQ) and feedback interface (PII)
The addressing scope of the control and feedback interface of the 4 IQ-SENSE
can be configured. You can select between
Standard
and
Enhanced
.
Standard properties
•
The 4 IQ-SENSE occupies 4 bits in the feedback interface.
•
The switching state for every channel can be evaluated via the feedback
interface.
Enhanced properties
•
The 4 IQ-SENSE occupies 1 byte in the control interface and 1 byte in the
feedback interface
•
The sensitivity/distance values for every channel can be preset with the control
interface (
IntelliTeach
via FB ”IQ-SENSE Opto”) and
Teach-in
conducted.
•
The learnt sensitivity/distance value /switching threshold) and the switching
state can be evaluated for every channel via the feedback interface.
Requirements:
•
The ”IQ-SENSE Opto” function block can be used. The function block enables
easy access to the control and feedback interface.
•
Please note that in this case PII is the same as PIQ.
•
The function block and the associated product information can be downloaded
from
http://www.ad.siemens.de/csi_e/gsd
Configuring address space
Address
space
STEP 7 as of V5.1, ServicePack 3
STEP 7 as of V4.2 or COM
PROFIBUS or other
configuration software
Standard
Select the entry
4IQ-SENSE Opto S
in the HW CONFIG hardware
Select the entry
S 6ES7 138-4GA00-0AB0
in the HW CONFIG hardware
catalog
S 6ES7 138-4GA00-0AB0
IQ-SENSE Opto from the GSD file
Enhanced
Select the entry
4IQ-SENSE Opto E
in the HW CONFIG hardware
Select the entry
E 6ES7 138-4GA00-0AB0
in the HW CONFIG hardware
catalog
E 6ES7 138-4GA00-0AB0
IQ-SENSE Opto from the GSD file
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...