Table 6-21 1POS INC/Digital, 1POS SSI/Digital, 1POS INC/Analog, 1POS SSI/Analog
Error type
Meaning
Remedy
1
D
00001: Short circuit
Short circuit of the sensor
supply.
Check the wiring to the sensor.
Correct the process wiring.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
17
D
10001: Load voltage 2L+
missing
Only applies to the 1POS
INC/Digital and 1POS
SSI/Digital:
No supply voltage, or
inadequate supply voltage.
Correct the process wiring.
Check the supply voltage.
26
D
11010: External fault
Wire break/short circuit of the
sensor signals.
Wire break in the sensor cable
or sensor cable is not
connected.
Sensor is defective or there are
faults.
Sensor type, transmission rate,
and monoflop time do not
correspond to the sensor
connected; programmable
sensors do not correspond to
the settings on the module.
Correct the process wiring
Correct the parameter settings
Replace the sensor.
Serial interface module 1SI 3964/ASCII, 1SI Modbus/USS
Table 6-22 1SI 3964/ASCII, 1SI Modbus/USS
Error type
Meaning
Remedy
6
D
00110: Open circuit
Wire broken or disconnected.
Check the wiring to the
terminals. Check the cable to
the partner.
7
D
00111: Upper limit
violation
Buffer overflow; message
length overflow
The P_RCV FB must be called
more frequently.
8
D
01000: Lower limit
violation
Message of length 0 sent
1
Check why the communication
partner is sending frames
without user data.
9
D
01001: Error
Internal module error occurred.
Replace the module.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Correct the parameter
assignment.
22
D
10110: Message error
Frame error, parity error
Check the communication
settings.
1
EM 1SI: only with 3964(R)
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...