Functions and Technical Specifications
4-7
EM 148-FC
Frequency Converter
A5E00065321-03
4.2
Parameters
4.2.1
Parameters of the Frequency Converter
The parameter names listed in bold in the tables are explained in further detail in
Section 4.2.2.
Table 4-5
Parameters of the Frequency Converter
Parameters
Possible settings
Parameter values via
DDB file
Default
Reaction to
CPU-/master-STOP
Rapid stop
Ramp down
Coast to a standstill
Keep last value
Coast to a
standstill
Diagnostic interrupt
Disable
Enable
Disable
Operation in
Europe/USA
EUR
USA
EUR
Rated frequency of motor
50 Hz
60 Hz
50 Hz
Rated voltage of motor
120 V
230 V
400 V
460 V
500 V
400 V
Rated current of motor
0.1 ... 4.0 A
(resolution 0.1 A)
1 ... 40 (* 0.1 A)
4.0 A
Rated speed of motor
0 ... 5000 min
–1
(resolution 20 min
–1
)
0 ... 250 (* 20 min
–1
)
1400 min
–1
Rated power of motor
0.1... 1.5 kW or
0.1... 2.00 hp (resolution
0.01 kW or hp)
0.1... 150 (* 0.01 kW) or
0.1... 200 (* 0.01 hp)
1.5 kW or 2 hp
Thermistor monitoring
of motor
Disable
Enable
Disable
Содержание SIMATIC EM 148-FC