5-10
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
You can use the scanning rate factor to specify that the counting value does
not change until the stated number of encoder pulses has occurred.
This increases the counting range of the encoder pulses by a multiple of the
scanning rate factor.
Evaluation of the channel--specific scanning rate factors must be enabled
with the
²
scanning rate
²
group bit.
When a counting procedure starts, the scanning rate factor is always started
again. The remaining pulses are not carried over from the previous counting
procedure.
Counting
value
Encoder pulses
Counter start
Counter stop
0
0
1
1
1
1
0
0
1
1
0
1
Counting pulses
Counter start
Figure 5-8
Generation of the counting value with a scanning rate factor of 3
(counting up)
Enabling of a scanning rate factor applies to all channels.
Table 5-7
Scanning rate
Variable
Parameter
Block
Offset
Data
Type
Value Range
Scanning
Rate
2
7.7
Bool
0: Scanning rate not enabled
1: Scanning rate enabled
The scanning rate factor can be specified for each channel.
If you specify
²
0
²
or
²
1,
²
the channel does not use the scanning rate.
Table 5-8
Scanning rate factor
Variable:
Scanning Rate Factor
Parameter
Block
Offset
Data
Type
Value Range
ScanRate_F_Chan_1
2
8.0
Byte
0 to 255
ScanRate_F_Chan_2
2
9.0
Byte
ScanRate_F_Chan_3
2
10.0
Byte
ScanRate_F_Chan_4
2
11.0
Byte
ScanRate_F_Chan_5
2
12.0
Byte
ScanRate_F_Chan_6
2
13.0
Byte
ScanRate_F_Chan_7
3
2.0
Byte
ScanRate_F_Chan_8
3
3.0
Byte
Scanning rate
Pulse Counter Operating Mode
Содержание SIMATIC CM35
Страница 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Страница 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Страница 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Страница 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Страница 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Страница 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Страница 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Страница 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Страница 88: ...6 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Period Duration Measurement Operating Mode 6 ...
Страница 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Страница 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Страница 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Страница 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Страница 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Страница 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...
Страница 141: ...Glossary 6 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Glossary ...