66DL2804-3xxxx or 6DL2804-4xxxx
Equipotential bonding rail
3 x 10 mm galvanized Cu with terminals 4 to 35 mm²
Protective conductor connector
M8 screw, at least 16 mm² with cable lug
Rated voltage/current
2)
Max. 1 000 V / 100 A
Operating temperature range
3)
-20 °C to +xx °C or -40 °C to +xx °C
4)
or 0 °C to xx °C
Permissible humidity
Max. 95%
1)
The degree of protection of the enclosure depends on that of the installed parts and the enclosure size.
2)
The actual electrical values depend on the electrical equipment installed. The manufacturer specifies the final values within
the framework of these limits.
3)
The specified permissible operating temperature range is only valid if the enclosure is installed horizontally. A vertical
installation can reduce the maximum permissible temperature. The max. operating temperature is defined depending on
the dissipated heat of the installed components, and specified on the nameplate.
Note that the operating temperature of the complete setup must be checked again if further components are subsequently
fitted.
4)
The temperature range of -40 °C is only possible when a heater is installed (see also Section 4.5).
Technical specifications
Distributed I/O 6DL2804-3xxxx & 6DL2804-4xxxx
30
Hardware Installation Manual, 04/2017, A5E41591350-AA