Wiring
5.11 Connecting the supply voltage to the CPU/interface module
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
99
5.11
Connecting the supply voltage to the CPU/interface module
Introduction
The supply voltage of the CPU/interface module is supplied by means of a 4-pin connector
plug located on the front of the CPU/interface module.
Power supply unit
Only use power supply units of type SELV/PELV with safe electrically isolated functional
extra low voltage (
≤ 28.8 V
DC).
Connection for supply voltage (X80)
The connections have the following meaning:
①
Ground of the supply voltage
②
Ground of the supply voltage for looping through (permitted value 10 A)
③
+ 24 V DC of the supply voltage for looping through (permitted value 10 A)
④
Spring release
⑤
+ 24 V DC of the supply voltage
1L+ and 2L+ and 1M and 2M are internally jumpered.
Figure 5-11 Supply voltage connection
The maximum cross-section of the connection is 2.5 mm
2
. A strain relief is not present. The
connector plugs provide you with the option of looping the supply voltage through without
interruption, even when it is unplugged.
Requirements
●
Only wire up the connector plug when the supply voltage is turned off.
●
Follow the wiring rules (Page 87).
Required tools
3 to 3.5 mm screwdriver