Maintenance
12.6 Firmware update
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
249
Procedure using the SIMATIC memory card
Proceed as follows to perform a firmware update via the SIMATIC memory card:
1.
Insert a SIMATIC memory card into an SD card reader of your programming device /
computer.
2.
To store the update file on the SIMATIC memory card, select the SIMATIC memory card
in the "Card Reader/USB memory" folder in the project tree.
3.
Select the "Card Reader/USB memory > Create firmware update memory card"
command in the "Project" menu.
4.
Use a file selection dialog to navigate to the firmware update file. In a further step you can
decide whether you want to delete the content of the SIMATIC memory card or whether
you want to add the firmware update files to the SIMATIC memory card.
5.
Insert the SIMATIC memory card with the firmware update files into the CPU.
Point to note when updating firmware for analog modules and the IO-Link Master CM 4xIO-
Link communication module
If you want to update firmware for analog modules or the IO-Link Master CM 4xIO-Link
communication module, you must supply a load current of 24 V DC to the modules through
the infeed element.
Procedure
1.
Remove any inserted SIMATIC memory card.
2.
Insert the SIMATIC memory card with the firmware update files into the CPU.
3.
The firmware update begins shortly after the SIMATIC memory card has been plugged in.
4.
Remove the SIMATIC memory card after the firmware update has been completed.
The RUN LED on the CPU lights up yellow, the MAINT LED flashes yellow.
If you then use the SIMATIC memory card as program card, delete the firmware update files
manually.
Note
If your hardware configuration contains several modules, the CPU updates all affected
modules in the slot sequence, which means in ascending order of the module position in the
STEP 7 device configuration.
Procedure using the Web server
The procedure is described in the Web server
http://support.automation.siemens.com/WW/view/en/59193560
) function manual.